GridLinksRequest a Quote

Engineering calculator

Cable current & voltage drop

Three-phase voltage drop using cable resistance and reactance.

Inputs

Results

Load current
386.45A
Voltage drop
14.26V
Voltage drop
3.44%

Compare with the limit applicable to the installation (AS/NZS 3000 allows 5% overall for LV unless otherwise specified).

ΔV = √3 × I × L × (R cos φ + X sin φ)

Assumptions

  • Balanced three-phase load
  • R and X from manufacturer data or AS/NZS 3008.1.1

Limitations

  • Does not check current-carrying capacity, derating or fault withstand
  • Motor starting drop not included

References: AS/NZS 3008.1.1 · AS/NZS 3000

Provided for general information. Gridlinks Solutions accepts no liability for decisions made using this calculator without independent engineering verification.