Engineering calculator

Capacitor bank sizing

Reactive compensation needed to correct to a target power factor.

Inputs

Results

Required compensation
236.8kVAr
kVA reduction
114.7kVA

Qc = P × (tan φ1 − tan φ2)

Assumptions

  • Constant active power

Limitations

  • Resonance with network harmonics must be checked — detuned reactors may be required
  • Switching transients and step sizing not addressed

References: IEC 60831 · IEC 61921

Provided for general information. Gridlinks Solutions accepts no liability for decisions made using this calculator without independent engineering verification.