Earthing conductor sizing (adiabatic)

Minimum conductor cross-section to withstand an earth fault for a given duration.

Inputs

Results

Minimum cross-section
174.8mm²
Next standard size
185mm²

S = I × √t / k

Assumptions

  • Adiabatic heating (no heat loss during the fault)
  • k = 143 is typical for PVC-insulated copper starting at 30 °C; use the k value for your material, insulation and temperature limits

Limitations

  • Conductor sizing only — does not verify touch/step voltages or grid resistance
  • Backup protection clearing time should be used for grid conductors

References: AS/NZS 3000 · IEEE 80 · AS 2067

Provided for general information. Gridlinks Solutions accepts no liability for decisions made using this calculator without independent engineering verification.