Engineering calculator

Transformer secondary fault current

Three-phase symmetrical fault current at transformer secondary terminals, with optional source impedance.

Inputs

Results

Fault current (infinite source)
26.67kA
Fault current (with source)
24.69kA
Fault level
18.52MVA

Isc = V / (√3 × (Zt + Zs)), Zt = Z% × V² / S, Zs = V² / Ssource

Assumptions

  • Symmetrical RMS bolted three-phase fault
  • Impedances added arithmetically (conservative)
  • No motor contribution

Limitations

  • Not a substitute for a full short-circuit study to IEC 60909
  • Excludes DC offset / peak make current
  • Earth-fault levels require sequence impedances

References: IEC 60909-0 · AS/NZS 3000

Provided for general information. Gridlinks Solutions accepts no liability for decisions made using this calculator without independent engineering verification.