GridLinksRequest a Quote

Engineering calculator

MV cable charging current

Capacitive charging current of a screened MV/HV cable.

Inputs

Results

Charging current per phase
8.98A
Charging reactive power
0.513MVAr

Ic = 2π × f × C × (V / √3) × L

Assumptions

  • Capacitance from manufacturer datasheet

Limitations

  • Breaker capacitive switching duty and earth-fault compensation need separate assessment

References: IEC 60502-2 · IEC 62271-100

Provided for general information. Gridlinks Solutions accepts no liability for decisions made using this calculator without independent engineering verification.